Performance
Specs
Flow Accuracy:
± 1% of reading ± 0.2 % of full scale*
* Point velocity for insertion flowmeters. Fox recommends a
minimum of 15 diameters of straight pipe upstream of the flowmeter
and 10 diameters downstream for insertion flowmeters. Fox
recommends a minimum of 8 diameters of straight pipe upstream of
the flowmeter and 4 diameters downstream for inline
flowmeters.
Flow Repeatability:
± 0.2% of full scale
Flow Response Time:
0.9 seconds (one time constant)
Temperature Accuracy:
± 1.8° F (± 1.0° C) over -40 to 250° F (-40 to 121° C); ± 3.6° F
(± 2.0° C) over 250 to 650° F (121 to 343° C). Minimum velocity 60
SFPM.a
Operating
Specs
Units of Measurement:
SCFM, SCFH, NM3/hr, NM3/min, Kg/hr, Kg/min, Kg/sec, Lbs/d, Lbs/hr,
Lbs/min, Lbs/sec, NLPH, NLPM, SLPM, SMPS, NMPS, SFPM, MMSCFD
Flow Rates for Insertion Flowmeter:
0 to 32,000 SFPM (163 NMPS) - Air at 70F & 1 ATM
To determine if an Insertion Flowmeter will operate properly,
divide the maximum flow rate by the pipe area. The application is
acceptable if the velocity is within the velocity range
above.
Gas Pressure (maximum):
500 psig (34.5 barg)
Insertion Flowmeter:
Note: Pressure ratings stated for temperature of 100°F
(38°C).
Temperature:
Std sensor: -40 to 250°F (-40 to 121°C)
HS Sensor: 32 to 400°F (0 to 204°C)
HT Sensor: 32 to 650°F (0 to 343°C)
Enclosure: -40 to 158°F (-40 to 70°C) without display, 32 to
140°F, (0 to 60°C) with display
Input Power:
24 VDC, ± 10%, 0.75 amp standard
Output:
Two isolated 4 to 20 mA outputs (1 for flow & 1 for
temperature); isolated pulse output 0 to 100Hz, 10 volts p/p for
flow (the pulse output can be used as an isolated solid state
output for alarms)
RS232 for connecting a Palm Handheld or computer; RS422/
RS485-Modbus, Profibus-DP, DeviceNet or Ethernet
Physical
Specs
Sensor material:
316 stainless steel standard; Hastelloy C276 optional
Enclosure:
FM (U.S.) & FMc (CANADIAN) approved for Class I, II, III,
Division 2, Groups A, B, C, D, E, F, G, T4A hazardous locations.
NEMA 4X and CE approved.
Options: Remote NEMA 4X electronics enclosure with explosion-proof
sensor j-box.
Cabling:
Remote enclosure: 5-conductor, 18 AWG, twisted, shielded, 100 feet
maximum
Packing gland assembly: 125 psig (8.6 barg ) max. (See Figure
6)
High pressure (crank) retractor: NPT 600 psig (41.4 barg), ANSI
150 flange & ANSI 300 flange, no valve supplied. (See Figure
7)
Dimensional
Insertion Flowmeters:
Probe diameter: 1/2"
Equation for selecting Insertion Flowmeter probe
length:
Probe length = ½ pipe ID (in inches) + 2" + thickness of
insulation (if any) + dimension of retractor (if supplied). Round
up to the next standard probe length available.