
Types of Compressed Air
Systems
There are two main types of
compressed air systems: oil-free and lubricated. One design
will be chosen over the other, depending on purification and
industry requirements. Air purification requirements include
general purity, instrument quality, breathing air, medical air,
pharmaceutical, and clean dry air.
Oil-Free Systems:
Applications that cannot tolerate a lubricant require an oil-free
system. It is critical to remove unwanted oil aerosols and vapors
from compressed air, not just moisture. These aerosols and vapors
are found in ambient air and can be generated by the compressor.
This oil ends up degraded and oxidized by the heat of compression.
Once heated, the oil can carbonize and form a solid, varnish-like
substance on downstream equipment, causing valves and air tools to
malfunction. If the oil is mixed with water, it forms a sludge that
can gum up components of the air line. Downstream from the
compressor, an air receiver stabilizes system pressure, serves as a
demand reservoir, and holds some moisture. Downstream from the
receiver, an air dryer, which will provide the correct pressure dew
point, traps the remaining moisture. If either of these fail, there
is still a coalescing filter after the dryer to provide protection.
A dry receiver can also be installed after the coalescing filter to
stabilize pressure and serve as a reservoir for times of high
demand.
Lubricated Systems:
These types of systems use a lubricant to alleviate friction
between moving parts. In rotary screw compressors, the lubricant
also seals clearances and removes heat of compression. The
viscosity of the lubricant used depends largely on the operating
ambient temperature range. It must offer adequate lubrication for
bearings and rotors at operating temperature. In addition, it must
have a pour point low enough to provide fluidity at low starting
temperature. A modern, lubricated rotary screw compressor and
high-efficiency purification system can produce compressed air with
very high purity. These systems are very similar to the oil-free
system, consisting of a wet receiver, an air dryer, and a
coalescing filter. There is, however, a charcoal filter between the
coalescing filter and the dry receiver that removes any leftover
oil vapors.
Compressed Air System
Design and Configuration
There are eight basic elements that
must be considered in designing your compressed air system: demand,
compressed air quality, supply, storage, distribution,
installation, maintenance, and condensate management
Demand
One of the most important and most difficult things you can do
when designing your compressed air system is to determine the true
demand in your system. Air demand will fluctuate beyond the
predetermined average demand. If the actual demand is known,
storage and distribution systems can be designed to meet demand
without the installation of additional compressors.
The most precise way to determine
demand in the system is to monitor the air flow using a flow meter,
which would normally be positioned in the main headers. For small,
simple systems, the ratio between loaded and unloaded compressor
running time can be indicative of average demand over a long
periods of time.
Often, leakage and artificial demand
represent a substantial portion of the overall demand. There are
various methods to stop leaks. Excess volume of compressed air
created for unregulated users is called artificial demand. It
occurs when greater line pressure than necessary was supplied. It
includes the following:
- all unregulated consumption,
including appropriate and inappropriate production
usage
- open blowing
- leaks
- point of use with regulators
adjusted to their maximum setting
- tooling
These applications track the supply
pressure as though no regulators were being used. The artificial
demand challenge can be resolved by positioning a regulator at the
point of use or at the beginning of the distribution network.
Operating pressure requirements, compressed air requirements, and
the duty cycle of individual equipment must all be considered when
establishing demand for your system.
Air quality: Different applications
demand different levels of compressed air quality. With each level,
the cost to produce the compressed air increases. Therefore, it is
essential to meet, but not exceed the level required by your
particular application. If different levels are required for
different applications within the plant, it is more cost-effective
to treat smaller amounts of compressed air for the application with
the highest level of quality requirements, than to treat the whole
air supply.
Levels of Compressed Air
Quality |
Level |
Application |
Air Treatment Components |
Function |
1 |
Shop Air |
Filtered Centrifugal Separator |
Removes solids 3 microns & larger, 99% of water droplets,
& 40% of oil aerosols |
2 |
Air Tools, Sand Blasting, Pneumatic Control
Systems(indoor) |
Refrigerated Compressed Air Dryer, Air Line Filter |
Removes moisture producing a 35° to 50°F (-1.67° to 10°C)
pressure dew point, removes 70% of oil aerosols, and all particles
1 micron and larger |
3 |
Instrument Air, Paint Spraying, Powder Coating, Packing
Machines |
Refrigerated Compressed Air Dryer, Oil Removal Filter |
Removes moisture & produces a 35° to 50°F (-1.67° to 10°C)
pressure dew point, removes 99.999% of oil aerosols, and all
particles .025 microns and larger |
4 |
Food Industry, Dairy Industry, Laboratories |
Refrigerated Compressed Air Dryer, Oil Removal Filter, &
Oil Vapor Adsorber |
Removes moisture & produces a 35° to 50°F (-1.67° to 10°C)
pressure dew point, removes 99.999% of oil aerosols, all particles
.025 microns and larger, oily vapor, oily smell, & oily
taste |
5 |
Outdoor Pipelines, Pneumatic Transport of Hygroscopic Material,
Breweries, Chemical & Pharmaceutical Industry, Electronics
Industry |
Air Line Filter, Oil Removal Filter, Low Dew Point Desiccant
Dryer, Air Line Filter |
Removes moisture producing a -40° to -150°F (-40° to -101.11°C)
pressure dew point, removes 99.999% of oil aerosols, and all
particles .025 microns and larger |
6 |
Breathing Air |
Breathing Air System (Continuous or Portable) |
Removes harmful compressed air contaminants and will produce
Grade D breathing air Figure CAS1-1: Levels of Compressed Air
Quality |
Supply
The compressed air supply must always meet the compressed air
demand by utilizing sufficient storage and correct distribution.
Properly sized compressors and purification equipment will aid in
meeting demand with supply. If the supply, storage, and
distribution are not in sync, excessive pressure fluctuation will
occur. Most compressors are controlled by line pressure. A drop in
pressure normally signifies a demand increase. This is corrected by
increased compressor output. A rise in pressure usually indicates a
decrease in demand, which causes a reduction in compressor output.
To accommodate the fluctuating demand, a load/no load or constant
speed control can be used to run the compressor at full load or
idle. Either a single compressor or a multiple compressor
installation, which can be centralized or decentralized, can
provide the entire plant supply. There are three other types of
compressor control systems:
- Auto-dual control:
Most traditional modulating controls throttle the capacity 30%-50%
before fully unloading the compressor. This type of modulation is
known as auto-dual control. It combines start/stop and constant
speed control into a single control system. Auto-dual control
automatically selects the most desirable control method and runs
the compressor in constant speed control. When the compressor
unloads, an unloaded run timer energizes, which usually has a time
range of 5 to 60 minutes. If the compressor does not reload, the
timer will shut the compressor off. The compressor will restart and
reload when the pressure switch senses low pressure.
- Sequencing:
Sequencing is also known as a central controller. This has the
advantage of little cost per compressor and is usually available
for systems with up to 10 compressors. A sequencer should have a
single pressure transducer in the air header. Logic should maintain
a target pressure within +/- 5 psi. The sequencer should
automatically start and stop compressors, as well as load and
unload them. The control should be set to rotate the order of
loading and unloading to optimize compressor combinations for
different demand conditions.
- Lead/Lag: Lead/lag
controls are typically found on reciprocating compressors. When
there are two compressors in the system, one compressor can be set
as the lead compressor, and the other as the lag compressor. When
the pressure drops to a certain point on the lead compressor, the
lag compressor will then take over. These can also be switched so
that the other compressor is the lead
compressor.
Storage
All devices containing compressed air make up the storage system.
Adequate storage is essential. It represents available energy that
can be released or replenished at any time it is needed. The air
receiver tank normally makes up the majority of the total storage
capacity of the system. If this tank is properly sized, excessive
cycling will be prevented, and adequate storage capacity for any
peaks in demand will be provided. In the distribution system, there
will periodically be large volume demands, which will rapidly drain
the air from surrounding areas, and cause pressure levels to fall
for surrounding users. However, strategically located receivers in
the system can supply these abrupt demands and still provide a
consistent air flow and pressure to the affected areas. The total
storage capacity needed is dependant upon the amount of excess
demand in cubic feet, the available pressure differential between
the flow controller, the system and compressor start-up time, and
the time available to replenish stored compressed air.
Distribution
The distribution system is the link between supply, storage, and
demand. Ideally, the distribution system will allow the required
air to flow with minimum pressure drop. It will supply an adequate
amount of compressed air at the required pressure to all of the
locations where compressed air is needed. The compressed air
travels through a network of pipelines, but the flow creates
friction and results in pressure drop. The pressure drop should
never exceed 1-2 psi (0.07 - 0.14 bar). The longer and smaller
diameter the pipe is, the higher the friction loss. To reduce
pressure drop effectively, a loop system with two-way flow can be
used. Pressure drop caused by corrosion and the system components
themselves are important issues. These typically range from 5-25
psid (0.34 - 1.7 bar) and their control is essential for the
efficiency of the system.
Installation
To effectively control and manage the compressed air system, the
system layout must be considered. Sufficient ventilation,
foundation and compressor room requirements must be met, and
appropriate piping materials used. Compressor intakes located
outdoors should be a minimum of 10 feet (3 meters) above grade.
Proper ventilation may be achieved through natural ventilation,
forced ventilation with an exhaust fan, ducted ventilation to the
outside with or without a recirculating damper, as well as by
mixing warm air with cold intake air, or venting an exhaust air
duct to the outside during summer (space heating during winter).
Foundation requirements apply only to larger reciprocating
compressors, but all compressors should have their own clean, cool
room. Piping must be durable enough for existing work conditions,
provide minimum possible pressure loss and leakage, and be easy to
maintain.
Maintenance
Preventive maintenance is the most important step you can take.
Leaks are one of the biggest maintenance issues and can be very
expensive. For example, one ¼" (6.35 mm) diameter opening equals
100 CFM (2.8 m3/min) at 90 psig (6.2 bar). This is equivalent to
running a 25 horsepower (18 kW) compressor. However, developing a
formal program to monitor and repair leaks can control or prevent
them. If a leak goes undetected, it can eventually cause the entire
system to have to be shut down. A well-maintained compressor, in
addition to having less downtime and repairs, will save on
electrical power costs as well.
Condensate
Control
Moisture in the form of liquid and vapor is in compressed air as
it leaves the system. The system can lose productivity and require
significant maintenance if the moisture and other contaminants are
not removed properly. Purification devices have been developed to
help remove some of the contaminants from the system. As pneumatic
applications and compressed air systems become more sophisticated,
the proper selection of these devices is crucial. The most critical
devices for condensate control are the coalescing filter, drain
valve, air dryer and after filter.
Note: All compressor condensate is to
be disposed of in accordance with all local, state and federal
regulations.
Energy
efficiency
Compressed air costs are a
significant component of most companies' utility costs. In many
cases, companies are paying much more than they have to. This is
because they are not operating their compressed air systems at the
greatest efficiency. There are six steps that can be taken to
reduce energy waste and increase energy savings:
- Evaluate your costs for compressed
air. To do this, add up all the compressor horsepower, calculate
the average air demand, and determine the percentage of full load
power.
- Identify the volume of wasted air.
This is accomplished by checking the leakage rate during off
periods, determining required point of use pressure, and
calculating wasted air through "over" pressurization.
- Calculate specific performance at
rated pressure, compare it with different brands, and select the
most efficient compressor control. Turn the control selector switch
to Dual Control, or check with the manufacturer for retrofit.
- Reduce the pressure drop in your
compressed air system. You can do this by measuring the pressure
drop at the maximum flow across all of the system components. After
that, increase the pipe size of the loop piping system, properly
maintain the filters, drain valves, dryers, and compressors.
- Stabilize and/or reduce the system
pressure downstream of the air drying equipment. Installing a flow
controller in conjunction with additional air receivers will
accomplish this. Use the 2-4 gallon receiver capacity/CFM, and
install a sequencer in multiple compressor installations.
- Evaluate the potential for heat
recovery. Explore applications that involve heating, analyze
existing costs for these applications, and implement a compressor
duct system or liquid/oil heat exchangers.
Compressed Air
Challenge:
The Compressed Air Challenge is a
voluntary cooperative of many organizations that deal with
compressed air systems in somecapacity, such as users,
manufacturers, distributors, system operators, consultants, state
research agencies, energy efficiency organizations, and other
utility companies. Their purpose is to provide the consumer with
information that will improve the performance of their compressed
air systems, resulting in higher overall operating efficiency and
lower energy costs. Ultimately, net profits may be increased
through compressed air system optimization.
Air System
Maintenance:
Maintenance
Preventive maintenance is the most
important step you can take. Leaks are one of the biggest
maintenance issues and can be very expensive. For example, one ¼"
(6.35 mm) diameter opening equals 100CFM (2.8 m3/min) at 90 psig
(6.2 bar). This is equivalent to running a 25 horsepower (18 kW)
compressor. However, developing a formal program to monitor and
repair leaks can control or prevent them. If a leak goes
undetected, it can eventually cause the entire system to have to be
shut down. A well-maintained compressor, in addition to having less
downtime and repairs, will save on electrical power costs as well.
Selection and purchase of the compressor and necessary purification
equipment can be easily done on the eCompressedAir site. Our
application engineers are ready to answer all of your questions and
to assist you in placing your order.
Industry's Fourth
Utility:
Compressed air is considered to be
industry's fourth utility. It is an energy source that, like
electricity, water, and natural gas, allows people to operate
equipment, tools, and processes safely and efficiently. Many
businesses would experience losses in productivity and
profitability without dependable pneumatic power.
Rules of
thumb:
There are a few rules of thumb
regarding the efficiency of compressed air systems:
- At 100 psig (7 bar) discharge
pressure, most air compressors deliver 4-5 CFM per horsepower (0.11
- 0.14 m3/min per kW).
- Every 2 psig (0.137 bar) of pressure
changes the power draw of a compressor by 1%.
- Efficiency is affected by about 1%
for every 10°F change in inlet air temperature. Warmer temperature
decreases and colder temperature increases efficiency.
- A 50 hp (67 kW) compressor ejects
about 126,000 Btu per hour. It is possible to regain approximately
119,000 Btu per hour of this.
- The power cost for 1 horsepower for
three shifts, seven days a week (8,760 hours) at $.10/kWk equals
approximately $750/year.
- The control air receiver located
after the compressor should be sized for about 1 gallon capacity
per CFM of compressor capacity.
- To ensure an effective demand side
control management system, the storage air receiver should be sized
for about 2-4 gallon capacity per CFM of compressor capacity.
- Total pressure drop should not
exceed 15 psi (1 bar) across all compressed air system components,
including piping.
The following schematics may be
viewed for a visual representation of these systems:
Pharmaceutical facility air
systems
Compressed air systems used in pharmaceutical facilities have to
meet the requirements of ISA-S7.0.01-1996 and cGMP for validated
systems. Proper design of your compressed air system will meet
these requirements and reduce your utility cost up to 30 % by
optimizing the system. Proper selection of compressor, receiver,
filter, dryer, drain valve, piping and maintenance is key. There
are several types of air compressors and air dryers, which are the
heart of the system. They include non-lubricated positive
displacement (reciprocating and rotary), dynamic (centrifugal)
compressors and heat-less, heated (internal and external) dryers.
ECompressedAir can design and supply an AIR COMPRESSOR DRYER
PACKAGE that will meet your specific requirement.
Pharmaceutical fermentation
air systems
Fermentation air is a validated system that meets the requirements
of cGMP. Redundancy and by-pass systems are required to maintain
continuous flow, pressure (20 to 40 psig), and dew points (-20° to
-60°F, or -28.89° to -51.11°C). Due to variable flow conditions,
energy management controllers are required. By optimizing the
design of your system, this requirement can be met and reduce your
utility costs by up to 50 %. The proper selection of compressors,
chiller packages, dryers, filters, drain valves, piping,
instrumentation, and good maintenance can help you realize this
savings. There are several types of non-lubricated compressors, air
chillers, and air dryers. They include:
- non-lubricated positive displacement
(reciprocating and rotary)
- dynamic (centrifugal)
compressors
- air or water cooled chillers
- heated (internal or external) air
dryers.
eCompressedAir can design and supply
all components that will meet your specific requirements.
Pharmaceutical solvent batch
drying system
The solvent drying system is used to dry batches of solvents from
bulk transfer trucks or storage tanks. The system includes a single
sieve, drying column and closed loop, nitrogen regeneration system
consisting of a condenser, coolant pump, separator, filter,
re-circulation blower, and heater all piped and mounted on a common
skid. All pressure vessels meet the provisions of the ASME Boiler
and Pressure Vessel Code, Section VIII, Division I. All process
wetted components and piping are constructed of 316 L SS. The
drying and regeneration operations are completely automated and
sequenced by a microprocessor-based control system. The drying
cycle is started manually. All electrical components are suitable
for installation in a Class I, Division II, Group C & D
location. eCompressedair can design and supply solvent drying
systems that will meet your specific requirements.
Typical Performance
Conditions |
Solvent Batch Size: |
5000 gallons |
Solvent to dry: |
THF |
Solvent Flow Rate: |
10 gpm |
Inlet H2O: |
2000 ug/ml |
Outlet H2O: |
50 ug/ml |
Number of Batches: |
One batch before regeneration |
Cycle Time: |
48 hours (adsorption and regeneration) |
Purge Rate: |
10 scfm nitrogen |
Other solvents to be dried at the same
conditions with specific limitations: |
Acetonitrile |
Hexanes |
Chlorobenzene |
Isopropyl Alcohol |
Cyclohexane |
Isopropyl Acetate |
O-Dichlorobenzene |
Methycyclohexane |
Dimethoxymethane |
Methyl Tert Butyl Ether (MTBE) |
Dimethylformamide (DMF) |
N-Ethyl Pyrrolidone |
Ethanol |
N-Methyl Pyrrolidone |
Ethyl Acetate |
Toluene |
Heptanes |
Xylenes |